Exterior Steel Tank Overcoat Systems
Surface Preparation: Minimum surface preparation of bare steel and previously painted steel requires a cleanliness level as defined by SSPC-SP WJ-4/NACE WJ-4 Light Cleaning by use of Low Pressure Water Cleaning (LP WC) between 3,500 and 5,000 psi using a 0 degree rotating nozzle. If all visible contaminates, loose mill scale, loose rust and other corrosion products, and loose paint have not been removed, SSPC-SP2 Hand Tool Cleaning or SSPC-SP3 Power Tool Cleaning should be employed until the surface cleanliness definition is met. All surfaces shall be clean, dry and no less than 5°F above the dew point during application and cure (dry to recoat).
Option I (Dryfall System)
Spot Prime Bare/Corroded: Tnemec Series 118 | Uni-Bond Mastic at 6.0 to 8.0 mils DFT (spray-applied)
Full Prime/Tie-Coat: Tnemec Series 118 | Uni-Bond Mastic at 6.0 to 8.0 mils DFT (spray-applied)
Finish Coat: Series 1028 | Enduratone gloss or Series 1029 | Enduratone semi-gloss; 2.0 to 3.0 mils DFT per coat
Option II
Spot Prime Bare: Series 135 | Chembuild; 4.0 to 6.0 mils DFT
Tie-Coat: Tnemec Series 115 | Uni-Bond DF; 2.0 to 4.0 mils DFT
Finish Coat: Tnemec Series 1028 | Enduratone; 2.0 to 3.0 mils DFT
Option III
Spot Prime Bare: Series 135 | Chembuild; 4.0 to 6.0 mils DFT
Tie-Coat/Finish Coat: Series 30 | Spra-Saf EN;2.0 to 4.0 mils DFT per coat